The third in a series of eight case studies from the Product Quality Research Institute focuses on facility biocontainment and inactivation.


Pharmaceutical Technology
Volume 35, Issue 9, pp. 74-76

This case study on facility biocontainment and inactivation is the third of eight in a series put together by the Product Quality Research Institute Manufacturing Technical Committee (PQRI-MTC) risk-management working group. The series is meant to advance the understanding and application of the International Conference on Harmonization (ICH) Q9 Quality Risk Management guideline by providing actual examples of risk-management assessments used by the bio/pharmceutical industry. The introductory article and first case study, on defining design space, appeared in the July 2011 issue of Pharmaceutical Technology (1).

When a manufacturer produces two or more drug substances in the same manufacturing facility, the facility is considered to be multiproduct. The facility designs, operations, and controls related to the use for multiple products should provide for appropriate measures to prevent cross-contamination between products. These controls include the containment procedures used to prevent the release of hazardous agents within the facility.

There are numerous facility design and operational attributes that may significantly affect the quality of products being manufactured. These attributes include, but are not limited to, area classifications, open versus closed processing, utility-system design, cleaning validation/clean-in-place systems, rules regarding equipment sharing, and critical flows throughout the facility. Facility designs and operations should provide for appropriate segregation of products to prevent cross-contamination. For facilities with multiple products or processes, the impact of potential process or product failures on the other operations in the same facility should be evaluated.

The following case study on facility biocontainment and inactivation is the third of eight in a series put together by the Product Quality Research Institute Manufacturing Technical Committee (PQRI–MTC) risk-management working group. The series is meant to advance the understanding and application of the International Conference on Harmonization (ICH) Q9 Quality Risk Management guideline by providing actual examples of risk-management assessments used by the bio/pharmceutical industry. The introductory article explaining the history and structure of the series, as well as the first case study on defining design space, appeared in the July 2011 issue of Pharmaceutical Technology (1). The second study addressed functional equivalence for equipment replacement (2).

In the current case study, two existing manufacturing suites were proposed to be remodeled to accommodate and contain manufacturing operations involving bacterial fermentation through viable cells of Streptococcus pneumoniae, a pathogenic Biosafety Level 2 (BL2) organism. These suites were separate manufacturing areas located adjacent to mammalian cell culture manufacturing-processing areas. Regulatory guidance requires BL2-Large Scale (LS) waste and residues to be inactivated prior to exiting the manufacturing area (3). An inactivation autoclave was identified during the initial risk assessment as one of the primary means of inactivation of BL2 waste and process equipment prior to exiting the fermentation suite. The risk-review step in the risk-management process identified that there was only one inactivation autoclave in the fermentation suite and that alternative backup inactivation procedures were desired to maintain continuity of manufacturing operations during autoclave preventive- and corrective-maintenance activities.

This case study describes the evaluation of various backup inactivation procedures for operational feasibility and includes a demonstration of an appropriate level of inactivation of the BL2 waste and equipment.

Risk question and risk-assessment method

The risk question developed for the subject case study is: What are the appropriate backup inactivation methods (i.e., procedures) that are operationally feasible and provide an appropriate level of decontamination capability that can be utilized in the fermentation suite to inactivate BL2 waste and equipment when the inactivation autoclave is unavailable?

Selection of a backup inactivation procedure is a precise exercise requiring an objective evaluation of the effectiveness of proposed procedures at inactivating the BL2 organism along with demonstration of consistent execution of these procedures each time they are performed.

Hazards analysis and critical control points (HACCP) is a risk-assessment tool that can be proactively used to identify and implement process controls that consistently and effectively prevent hazards from occurring. HACCP involves evaluation of critical procedural limits and determination of how they will be achieved routinely. Because it is essential that the backup inactivation procedures prevent the release of the BL2 organism outside of the fermentation suite, HACCP was selected as the risk-assessment tool to use to determine the appropriate preventative controls.


ADVERTISEMENT

blog comments powered by Disqus
LCGC E-mail Newsletters

Subscribe: Click to learn more about the newsletter
| Weekly
| Monthly
|Monthly
| Weekly

Survey
Which of the following business challenge poses the greatest threat to your company?
Building a sustainable pipeline of products
Attracting a skilled workforce
Obtaining/maintaining adequate financing
Regulatory compliance
Building a sustainable pipeline of products
26%
Attracting a skilled workforce
29%
Obtaining/maintaining adequate financing
14%
Regulatory compliance
31%
View Results
Eric Langer Outsourcing Outlook Eric LangerBiopharma Outsourcing Activities Update
Cynthia Challener, PhD Ingredients Insider Cynthia Challener, PhDAppropriate Process Design Critical for Commercial Manufacture of Highly Potent APIs
Jill Wechsler Regulatory Watch Jill Wechsler FDA and Manufacturers Seek a More Secure Drug Supply Chain
Sean Milmo European Regulatory WatcchSean MilmoQuality by Design?Bridging the Gap between Concept and Implementation
Medicare Payment Data Raises Questions About Drug Costs
FDA Wants You!
A New Strategy to Tackle Antibiotic Resistance
Drug-Diagnostic Development Stymied by Payer Concerns
Obama Administration Halts Attack on Medicare Drug Plans
Source: Pharmaceutical Technology,
Click here